對1、在建筑物:施工層建筑物面積500內,配置泡沫滅火器不少于2個,每增加500,增加1個泡沫干粉滅火器。非施工層應當根據實際情況配置。
For 1, in the building: the construction area of the building area of 500 square meters, the configuration of foam extinguisher not less than 2, each increase of 500 square meters, add 1 foam dry powder extinguisher. The non construction layer shall be configured according to the actual situation.
2、材料倉庫:面積50以內,配置泡沫干粉滅火器不少于1個,每增加50增加泡沫干粉滅火器不少于一個,(如材料倉庫存放可燃材料較多,更應相應增加滅火器數量。)
2. Material warehouse: within 50 square meters of area, there are not less than 1 foam dry powder extinguishers. Each additional 50 square meters increase the number of foam dry powder extinguishers not less than one. (for example, if material stores store more flammable materials, the number of fire extinguishers should be increased correspondingly).
3、施工辦公室、水泥倉庫:面積在100以內,配置泡沫干粉滅火器不少于1個,每增加50增配泡沫干粉滅火器不少于一個。
3, construction office and cement warehouse: the area is within 100 square meters, and the foam dry powder extinguisher shall not be less than 1. Each additional 50 square meters will be added to the foam dry powder extinguisher not less than one.
4、木制作場:面積在50以內,配置泡沫干粉滅火器不少于2個,每增加50增配泡沫干粉滅火器一個。
4, wooden workshop: the area is within 50 square meters, and the foam dry powder extinguisher is not less than 2. Each increase of 50 square meters is equipped with foam dry powder extinguisher.
5、電工房、配電房、電機房:配備滅火器不少于1個。
5. Electric workshop, power distribution room and motor room: at least one fire extinguisher shall be equipped.
6、油料倉庫:面積在50以內,配置泡沫干粉滅火器不少于2個,每增加50增配泡沫干粉滅火器不少于一個。
6, oil depot: the area is within 50 square meters, and the foam dry powder extinguisher is not less than 2. Each increase of 50 square meters is added to the foam dry powder extinguisher not less than one.
7、可燃物品堆放場:面積在50以內,配置泡沫干粉滅火器不少于2個。
7, combustible goods piling yard: the area is within 50 square meters, and the foam dry powder extinguisher is not less than 2.
8、垂直運輸設備(包括電梯、塔式起重機)機駕室:配置泡沫干粉滅火器不少于1個。
8, vertical transport equipment (including elevators, tower cranes) lift room: equipped with foam dry powder extinguisher not less than 1.
9、臨時易燃易爆物品倉:面積在50以內,配置泡沫干粉滅火器不少于2個。
9, temporary flammable and explosive goods warehouse: the area is within 50 square meters, and the foam dry powder extinguisher is not less than 2.
10、值班室:配備泡沫滅火器1個、滅火器1個及一條直徑65CM長度25米的消防帶。
10. Duty room: equipped with 1 foam extinguishers, 1 fire extinguishers and a fire hose with a diameter of 65CM and a length of 25 meters.
11、集體宿舍:每25配備滅火器1個,如占地面積超過1000,應按每500設立1個2米的消防水池。
11. Collective dormitory: one fire extinguisher shall be equipped every 25 square meters. If the floor area exceeds 1000 square meters, a fire pool of 2 square meters shall be set up every 500 square meters.
12、廚房:面積在100以內,配置泡沫干粉滅火器3個, 每增加50增配泡沫干粉滅火器一個。
12, kitchen: the area is less than 100 square meters, and 3 foam dry powder extinguishers are installed. Each additional 50 square meters is added with foam dry powder extinguisher.
13、臨時動火作業場所:配置泡沫干粉滅火器不少于1個和其他輔助消防器材。化.
13. Temporary fire place: no more than 1 foam fire extinguishers and other auxiliary fire fighting equipment. Change